Product model: E5CN-HR2H03-W-FLK
Name: Temperature Controller
Brand: OMRON
Sort: User's Manual
File language: English
File size: 1.17MB
Name: Basic Unit(gradient temperature control)(See note 1.).
Power supply voltage: 24 VDC supplied from the End Unit.
No. of control points: 2.
Control outputs 1 and 2: Voltage output: 2 points (for SSR drive)(See note 2.).
Control outputs 3 and 4: Transistor output: 2 points(sourcing).
Auxiliary output: None E5CN-HR2H03-W-FLK.
Functions: Heater burnout alarm, 2 (See note 3.); Event inputs, None E5CN-HR2H03-W-FLK
Communications functions: G3ZA connection port,
RS-485 From End Unit, Port A, RS-485.
Input type: Thermocouple, platinum resistance thermometer,
analog voltage, and analog current selectable for each channel.
Terminal: M3 terminal.
Gradient Temperature Control to Achieve.
Consistent Layer Temperature.
Perform gradient temperature control ranging from 2 to 32 channels E5CN-HR2H03-W-FLK.
Perform 2-channel gradient temperature control for up to 16,
groups, or 32-channel gradient temperature control for up to 2 groups.
Set gradient temperature control or 2-PID control for each group.
Reduce design work for ladder programming with programless,
connections to Programmable Controllers. (The same feature,
as Standard-control EJ1 Models E5CN-HR2H03-W-FLK. ).
Connect directly to the G3ZA Multi-channel Power Controller,
using optimum cycle control for high-accuracy control with minimal noise. Control output: relay output.
Auxiliary output: -.
Heating wire break, SSR fault detection function: -.
Event input: -.
Communication: RS-485.
Terminal shape: main unit (no terminal unit).
Power supply voltage: AC100 ~ 240V.
DIN rail operation, high performance E5 / C series of the maintenance of the most suitable system connected with a touch screen /PLC and thermostat installation type.
DIN 85mm * 22.5MM width depth guide installation type, housed in the control cabinet of the thin slender body.
The terminal platform can be easily replaced, and the maintenance performance is improved.
Through the 50ms high speed sampling, suitable for the use of high speed heating.
Easy to connect with PLC through no program communication.
The use of communicationn adapter cable (sold separately) connected to the computer, without power supply connection
Set up。 It can be easily set by CX-Thermo (sold separately) E5CN-HR2H03-W-FLK.
With auxiliary output (maximum 2 points), event input (maximum 1 points), tthe basic function is complete E5CN-HR2H03-W-FLK.
The confirmation of a simple, eye-catching white PV display when starting or abnormal in the cabinet
(PV high 8.5mm).
Related products
OMRON
High performance temperature controller
E5CN-HR2HH03D-FLK
OMRON High performance temperature controller E5CN-HR2HH03D-FLK
Size: 48 x 48mm. Body: terminal type. Type: c
OMRON
High performance temperature controller
E5CN-HR2HB-W
OMRON High performance temperature controller E5CN-HR2HB-W
Size: 48 x 48mm. Body: terminal type. Categor
OMRON
High performance temperature controller
E5CN-HR2H01-W-FLK
OMRON High performance temperature controller E5CN-HR2H01-W-FLK
Size: 48 x 48mm. Body: terminal type. Categor
OMRON
High performance temperature controller
E5CN-HR2BFD
OMRON High performance temperature controller E5CN-HR2BFD
Size: 48 x 48mm. Body: terminal type. Type: c