Unit classification: CJ1 Special I/O Units.
Product name: Process Input Units,
(Isolated type Units with Universal Inputs).
Input points: 4 inputs.
Signal range selection:
Set separately for each input.
Signal range:Fully universal
inputs: Pt100, JPt100, Pt1000, K,
J, T, L, R, S, B, 4 to 20 mA, 0 to 20 mA,
1 to 5 V, 0 to 5 V, 0 to 10 V CRT1-ID16-1 UL Standards and CSA Standards.
Conversion speed (resolution): Conversion,
speed: 250 ms/4 inputs
CRT1-ID16-1
Accuracy at ambient temperature of 25°C:
Accuracy: Platinum resistance thermometer,
input: ±0.3% of PV or ±0.8°C, whichever,
is larger) ±1 digit max. Thermocouple input:
(±0.3% of PV or ±1.5°C, whichever is larger),
±1 digit max. *1 Voltage or current input:
±0.3% of F CRT1-ID16-1 UL Standards and CSA Standards. S. ±1 digit max.
External connection: Removable terminal block.
No. of unit numbers allocated: 1.
Current consumption: 5V, 0.32A; 24V, --.
Standards: UC1, L, CE.
A Single Unit Handling All Types of Inputs,
such as Temperature Sensor Inputs and,
Analog Signal Inputs (e.g., 4 to 20 mA or 1 to 5V).
A Unit supports four input channels,
each of which can be set to a
platinum resistance thermometer, thermocouple,
and DC signal (current, voltage) CRT1-ID16-1 UL Standards and CSA Standards.
All inputs are isolated. C500-IA I/O Unit AC Input 16 pts C500-IA222(3G2A5-IA222).
AC200-240V 10mA.Model: C200H-OA222V.
No. of points: 12 pts.
Specifications: 0.3A, 250VAC.Product name: CS1 CPU Backplane.
Specifications: For both CS/C200H-series Units,
2 slots(Note:Expansion Racks,
cannot be connected).
Appli cable CPU Unit: CS1 CPU Unit.
Basic I/O Units: CS-series Basic I/O Unit,
Yes; C200H series Basic I/O Unit, Yes;
C200H Group-2 High density I/O Unit, Yes.
Special I/O Units: CS-series Special I/O Unit,
Yes; C200H series Special I/O Unit, Yes.
CPU Bus Units: CS-series CPU Bus Unit, Yes.
Current consumption: 5V system, 0.11A;
26 V system, --.
Standards: U, C, N, L, CE.
Multi-application Controllers:
From High-performance Machine C,
Highly Reliable Process Control. Name: Compact Connectors.
Specifications: Inputs; 2 inputs; NPN.
Bit slave of smallest class in industry,
Innovation in wiring for any type of machinery.
Available in 2 types: 2-poinnt Bit Slave Unit,
and 4-point Bit Slave Unit CRT1-ID16-1 Manual.
Compact size for installation in limited space.
Save space and wiring since bit slave can be,
installed near I/O devices.
Industry first bit slave connectable with round,
cabless which can be easily purchased at a lower price CRT1-ID16-1 Manual.
Connectable with flat cables, too for easy wiring.
Cables are selectable depending on applications.