Terminal (wire connection): Push-In Plus Terminal.
Applicable output load: AC load.
Zero cross function: No.
Rated input voltage: AC/DC 48V.
Global standard size,
low profile slim I/O relay with width 6.2 mm,
slim I/O solid state relay.
Realized about 25% lower profile than conventional,
products, contributing to further miniaturization of the,
control panel G3RV-SR700-AL DC24 PDF datasheet
G3RV-SR700-AL DC24
Push-In Plus terminal blocks are used to save wiring work,
in comparison with conventional screw terminals.
(Wiring time is reduced by 60%* in comparison with,
traditional screw terminals.).
No screw loosening means maintenance-free application,
realizing high reliability.
Hand-free structure that holds an inserted flat-blade,
screwdriver to achieve easier wiring work for stranded wires G3RV-SR700-AL DC24 PDF datasheet.
Screw terminal is also stocked to meet the screw type needs.
Mounted relay or solid-state relay has a plug-in terminal.
that is difficult to bend at the time of exchange. Input terminals: Screwless clamp terminals (detachable).
Isolation method: Phototriaccoupler.
Zero cross function: Yes.
Operation indicator: Yes.
Alarm output: 2 outputs (Heater Burnout Detection,
SSR Short-circuit Failure Detection) G3RV-SR700-AL DC24 PDF datasheet.
Applicable load (See note.): 2 to 25 A, 100 to 240 VAC.
A New-concept SSR with Built-in.
Current Transformer.
Heater Burnout and SSR Short.
circuit Failure Detection.
Built-in Current Transformer (CT) helps reduce wiring steps.
Detects the burnout of any one of a group of heaters.
Detects the burnout of 3-phase heaters.
Detects SSR short-circuit failures.
Error detection level can be easily set with a switch.
Mounts to a DIN track or with screws.
Three types of input terminals available: M3 terminals,
screwless clamp terminals (detachable), or compact slotted,
screw terminals (detachable).
Certified for CSA and EN (TÜV).
The G3PF-2@@B-@@@ Series is UL certified. Name: Safety Controller.
Number of I/O: Safety inputs, 10; Test outputs, 6;
Safety outputs, Solid-state outputs: 16; Standard outputs, --.
Unit version: Ver.2.0.
Easy programming for complex safety control.
Stand-alone Safety Controller for small and mid-sized machinery.
Three types of CPU with different I/O size to suit the application.
Four types of Expansion I/O Units for hard--wired diagnosis or standard signals G3RV-SR700-AL DC24 PDF catalog.
Clear diagnosis and monitoring via Ethernet or Serial connection.
Various kinds of safety devices directly connectable like noncontact,
switches and safety mats.
Easy design, vverification, standardization and reusage of,
safety control by unique programming software G3RV-SR700-AL DC24 PDF catalog.
ISO 13849-1 (PLe/Category 4), IEC61508 (SIL3) certified.