LK Automation Limited
Home >> Download >> OMRON >> Catalog Download >> OMRON 61F-G1 PDF catalog 61F-G1 datasheet PDF datasheet

OMRON 61F-G1 PDF catalog 61F-G1 datasheet PDF datasheet

Product model: 61F-G1
Name: Basic type no float switch
Brand: OMRON
Sort: PDF datasheet
File language: English
File size: 1.97MB
Compact, Space-saving Plug-in Type Ideal,
for Pump Panels or Building into Equipment.
Large switching capacity: 5 A at 220 VAC (resistive load).
Easy to handle with DIN rail mounting.
Replace for maintenance without rewiring the socket. Improved update. Reduce standby power consumption, and then achieve lightweight 61F-G1 PDF datasheet.
Standby power consumption reduced to 85% of the company''s previous products 61F-G1 (61F-GN)
The quality is reduced to less than 85% of the company''s previous products. (61F-G3N, G4N)
With LED action display function, so that the state of action at a glance.
By improving the reliability of internal relays (tiny load 1mA DC5V), the PLC input becomes possible.
The electrode side terminals and other wiring terminals are separated, so the wiring operation is simple 61F-G1 PDF datasheet.
Installation method can choose the JEM agreement, DIN guide rail installation, screw installation in 3 ways.
G4N type, with a water tank and a water supply tank level display and prevent the function of automatic water idling caused by water shortage.
Package product name: 61F-G4N base * 1, 61F-11_ unit * 5 61F-G1 PDF datasheet.
Purpose: long distance use (4km). Type: General-purpose.
G2 models.
Compact, Space-saving Plug-in Type Ideal,
for Pump Panels or Building into Equipment.
Large switching capacity: 5 A at 220 VAC (resistive load).
Easy to handle with DIN rail mounting.
Replace for maintenance without rewiring the socket. Product name: Conductive Level Controller.
Model number: Relay contact (SPST-NO).
Battery (24 VDC) allows use in locations.
without AC power supply. AC sine-wave.
voltage between electrodes enables stable.
detection with no electric corrosion.
Outputs can be set to self-hold at ON or OFF using special circuits.
Adjustable sensitivity, with an operating resistance range of 0 to,
100 kΩ, allows use for a wide variety of liquids.
Relay contact chattering conventionally caused by waves elim,
inated using open colllector output, reducing contact wear 61F-G1 PDF catalog.
Meets CE marking and is a UL recognized component. 2 heat resistant devices.
Heat resistant device used as starting water tank water reducing alarm device.
Second control cabinet for presssurized water supply device is also supported 61F-G1 PDF catalog.
Water reducing alarming device of heat resisting type starting water tank installed in control cabinet.
Related products
OMRON
Connector relay box
XW3A-P643-G11
OMRON Connector relay box XW3A-P643-G11
Sensor type: 3 wire DC / DC PNP - the 2 wir
OMRON
Compact no float switch
61F-GNL 4KM
OMRON Compact no float switch 61F-GNL 4KM
Improved update. Reduce standy power consump
OMRON
Connector relay box
XW3A-P843-G11
OMRON Connector relay box XW3A-P843-G11
Sensor type: 3 wire DC / DC PNP - the 2 wir