CV500-MC Special I/O Unit Motion Control Servo Control 2 axis CV500-MC221.I/O points: 256 pts.
Program capacity(words): 7.2 K.
DM capacity (words): 6 K.
RS-232C port: YES.
Analog setting: YES.Model : C500-AP003.
Necessary for Handheld Programming Console.Model : C500-LK103.
PCF.Power supply: AC power supply CS1D-ETN21D Manual.
Output method: Transistor output source type.
Inputs points: 18 points
CS1D-ETN21D
Outputs points: 12 points.Unit type: CJ1 Special I/O Units.
Product name: Analog Input Unit.
I/O points: 4 inputs;
Signal range selection: Set separately for each input.
Signal range; Resolution: 1 to 5 V (1/10,000),
0 to 10 V (1/20,000), -5 to 5 V (1/20,000),
-10 to 10 V (1/40,000), and 4 to 20 mA (1/10,000) CS1D-ETN21D Manual.
Conversion period: 20 μs/1 point, 25 μs/2 points,
30 μs/3 points, 35 μs/4 points,
The Direct conversion is provided.
Accuracy at ambient temperature of 25°C:
Voltage: ±0.2% of F.S. Current: ±0.4% of F.S.
External connection: Removable terminal block.
No. of unit numbers allocated: 1.
Current consumption: 5V, 0.52A; 24V, --.
Standards: UC1, CE.
Consistent Microsecond Throughput:
Models with Direct Conversion Join the Lineup CS1D-ETN21D Manual.
Analog Input Units for converting analog input,
signals into binary data.
Analog Output Units for converting binary ,
data into analog output signals.
Model : C500-LK203.
RS-232C/RS-422.Model: C200HW-PD024 OMRON CS1D-ETN21D Installation Guide.
Supply voltage: 24VDC.
Comments: --.Applicable CPU Units: CQM1H-CPU51/61.
Mounting locations and number of Boards: 1 Board can be mounted in either slot 1 or slot 2 OMRON CS1D-ETN21D Installation Guide.
Dimensions: 25 × 110 × 107 mm (W × H × D).
Weight: 60 g max.Unit type: CS1 Special I/O Units.
Product name: Isolated-type,
Thermocouple Input Units.
points Input: 8 inputs.
Signal range selection:
Set separately for each input.
I/O type: R, S, K, J, T, L, B OMRON CS1D-ETN21D Installation Guide.
Conversion speed: 250 ms/8 inputs.
Externa connection: Removable erminal block.
No. of unit numbers allocated: 1.
Current consumption: 5V, 0.18A; 26V, 0.06A.
Standards: UC1, CE.
Provides the functionality of isolators,
power supplies, signal converters,
and other devices.
The Analog Input Unit converts analog,
input signals such as 1 to 5 V or 4 to 20mA,
into digital values, and takes the values,
scaled in industrial units, and transfers,
it to the CPU Unit as the process value.
Because of this, no ladder program is required,
at the CPU Unit for scaling.
The Analog Output Unit converts analog output set,
values from the CPU Unit to analog output signals,
such as 4 to 20 mA or 1 to 5 V, and outputs them.
The built-in functions, such as measurement value,
alarms, rate-of-change calculations, and square roots,
have enabled major savings in cost and spaace compared,
with previous systems CS1D-ETN21D .
High-resolution Models and 8-point Input Models are,
also available.
By combining the Units, logging/monitoring.
systems can be constructed,
or the Units can be used together with LCBs/LCCUs,
to construct complete process control systems CS1D-ETN21D Manual.
Parameters can be easily displayed and set in an,
easy-to-understand form without special tools.