Size: 48 x 48mm.
Body: terminal type.
Category: control output 1 point type (power supply AC100 ~ 240V).
Shell color: silver.
Control output: current output.
Control mode: standard or heating cooling.
Auxiliary output points: 2 points.
The failure detection function of the heater with the broken line and SSR: -.
Event input points: -.
Transfer output: output (using control output).
Communication: -.
General thermostat new high performance (high resolution, high speed, high precision input) type products.
Support simple operation, preventive maintenance, using a new type of liquid crystal, visual angle, contrast to enhance.
High resolution 5 bit display / can display 0.01 degrees C (to achieve a small size of 48 x 48mm).
High speed sampling period 60ms.
All models (thermocouple /Pt/ analog input switching), 1 machines to support a variety of sensors.
Add PV/SV state display function, to see the state of the thermostat.
(automatic / manual, RUN/STOP, alarm), interactive display PV/SV.
By supporting software (CX-ThermoVer.4.0) to carry out a simple function (AND/OR logic and delay),
Increase the control output ON/OFF number counting function, can predict the temperature controller internal relay fault
Size: 48 x 48mm.
Control output: linear current output.
Auxiliary output: -.
Power supply voltage: AC/DC24V.
Terminal type: insert type.
Input category: full range multi input.
Using large font PV display (white), improve visibility.
Selection, operation and setting.
Functional performance of input and output points OMRON E5CN-HC2-W.
Support for more extensive range of applications.
Using high PV 15
E5CN-HC2-W2mm display (white), improve visibility.
High speed sampling to achieve 50ms.
With auxiliary output (maximum 3 points), event input (maximum 4 points), the transmission output,
Remote SP input function, support for a variety of applications.
E5CC 60mm has a depth of slender body.
The use of communication adapter cable (sold separately) connected with a computer OMRON E5CN-HC2-W.
After that, no power supply connection can be set.
It can be easily set by CX-Thermo (sold separately).
Easy to connect with PLC through no program communication.
Combined temperature control device through component communication. Case color: Black.
Control output: Voltage output (for driving SSR).
Control mode *1: Standard or heating/cooling OMRON E5CN-HC2-W.
No. of auxiliary outputs: 2.
Detection of heater burnout, SSR failure, and heater overcurrent: --.
No. of event inputs: --.
Transfer output *2: --.
Communi cations: RS-485.
Previous model: Thermocouple input, --;
Resistance thermometer input, --.
New 48 x 24-mm Basic Temperature,
Controller with Enhanced Functions and,
Performance OMRON High performance temperature controller. Improved Indication Accuracy,
and Preventive Maintenance Function OMRON High performance temperature controller.
Indication Accuracy.
Thermocouple input: ±0.3% of PV (previous models: ±0.5%),
Pt input: ±0.2% of PV (previous models: ±0.5%),
Analog input: ±0.2% FS (previous models: ±0.5%),
Models are available with screw terminal blocks or screwless,
clamp terminal blocks.
A PV/SV-status display function can be set to automatically alternate,
between displaying the status of the Temperature Controller (auto/
manual, RUN//STOP, and alarms) and the PV or SV OMRON High performance temperature controller E5CN-HC2-W.
Preventive maintenance for relays in the Temperature,
Controller using a Control Output ON/OFF Counter.
Switch the PV display between three colorrs OMRON E5CN-HC2-W.
Compatible with Support Software (CX-Thermo version 4.2 or higher).
Eleven-segment displays.
Models are available with one or two alarm outputs.