Unit: Connector model.
I/O classification: Digital output.
Internal I/O common: PNP (+ common).
I/O points: 16.
I/O connections: Fujitsu connector.
Power supplyvoltage: 24 VDC.
I/O specification: 0.5 A, DC/transistor.
models are available.
disconnecting the wires.
DIN track mounting.
Input capacity: 16 points.
Rated current (ON current):
0.5 A/output, 4.0 A/common.
Internal I/O common: NPN.
Residual voltage: 1.2 V max.
(0.5 ADC, between each output,
terminal and the G terminal).
Leakage current: 0.1 mA max.
ON delay: 0.5 ms max.
OFF delay: 1.5 ms max.
Number of circuits per common: 16 points/common OMRON GT1-OD16ML-1.
Output indicators: LED display (yellow).
Isolation method: Photocoupler isolation
GT1-OD16ML-1
I/O power supply method: Supply by I/O power supply.
Unit power supply current consumption: 90 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
I/O power supply current con sumption: 5 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
Weight: 180 g max.
Expansion functions: Enabled OMRON GT1-OD16ML-1.
Output handling for communications errors:
Select either hold or clear.
Short-circuit protection function: No.
High-speed digital I/O terminal with the,
screw type terminal block for EtherCAT,
communications.
Detachable screw terminal block facilitates,
the maintenance.
The expansion unit can be connected.
(One expansion unit per one I/O terminal unit.)
Input/output point can be flexibly increased,
depending on the system OMRON GT1-OD16ML-1.
Input response time can be switched for,
high-speed processing.
Selectable node address setting methods:
setting with rotary switch and with tool software.
When setting the nodes with rotary switch,
setting is easy and node identification becomes,
possible for maintenance OMRON Digital I/O Units. Name: System Units; I/O Power Feed Unit.
Specifications: Use when the total current,
consumption of the I/O Power Supply exceeds 4 A,
or to make the I/O Power Supply a separate system OMRON Digital I/O Units.
Standards: CE, UC, L.
"Easy" and "Flexible" system expansion,
with linked CC-Link and CompoNet.
Branching is easily made with CompoNet.
Wiring material cost can be reduced OMRON Digital I/O Units.
Bit-level I/O distribution reduces,
wiring in the system.
A wide variety of CompoNet Slave Units,
contribute to system size reduction.
Seven-segment Display on the Gateway Unit,
helps to detect errors on site.
The Participation Flags and Communications,
Error Flags can be checked at the Host,
Controller to detect the location and,
content of the error. Name: Slice I/O Units; Counter Units.
Specifications: Counter inputs: 1,
External outputs: 1 PNP.
Standards: CE, UC, L.
"Easy" and "Flexible" system expansion,
with linked CC-Link and CompoNet.
Branching is easily made with CompoNet.
Wiring material cost ccan be reduced GT1-OD16ML-1.
Bit-level I/O distribution reduces,
wiring in the system.
A wide variety of CompoNet Slave Units,
contribute to system size reduction.
Seven-segment Display on the Gateway Unit,
helps to detect errors on sitee OMRON GT1-OD16ML-1.
The Participation Flags and Communications,
Error Flags can be checked at the Host,
Controller to detect the location and,
content of the error.