LK Automation Limited
Home >> Products >> OMRON >> Master slave station products >> EtherCAT remote I/O terminal >> GX-ID1621 OMRON GX-ID1621 EtherCAT Remote I/O Terminals

GX-ID1621 OMRON GX-ID1621 EtherCAT Remote I/O Terminals

Brand: OMRON
Name: EtherCAT Remote I/O Terminals
Model: GX-ID1621
Input capacity: 16 points.
Internal I/O common: PNP.
ON voltage: 15 VDC min.
(between each input terminal and the G terminal)
OFF voltage: 5 VDC max.
(between each input terminal and the G terminal)
OFF current: 1.0 mA max.
Input current: 6.0 mA max./input (at 24-VDC);
3.0 mA min./input (at 17-VDC).
ON delay: 0.1 ms max.
OFF delay: 0.2 ms max.
Input filter value: Without filter, 0.5 ms, 1 ms,
2 ms, 4 ms, 8 ms, 16 ms, 32 ms (Default setting: 1 ms).
Number of circuits per common: 16 inputs/common.
Input indicators: LED display (yellow).
Isolation method: Photocoupler isolation.
I/O power supply method: Supply by I/O power supply.
Unit power supply current consumption: 90 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
I/O power supply current con sumption: 5 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
Weight: 180 g max.
Expansion functions: Enabled.
Short-circuit protection function: No.
High-speed digital I/O terminal with the,
screw type terminal block for EtherCAT,
communications.
Detachable screw terminal block facilitates,
the maintenance.
The expansion unit can be connected.
(One expansion unit per one I/O terminal unit.)
Input/output point can be flexibly increased,
depending on the system.
Input response time can be switched for,
high-speed processing.
Selectable node address setting methods:
setting with rotary switch and with tool software.
When setting the nodes with rotary switch,
setting is easy and node identification becomes,
possible for maintenance.

Input/Output: Inputs.
Internal I/O circuit common: PNP (– common).
I/O points: 8 points.
I/O connection method: Sensor connector.
Rated voltage for I/O power supply: 24 VDC.
Eight Waterproof Terminal Models.
Emphasizing Cost Efficiency.
Reduced Labor.
Connection using connectors reduces the lead time,
required for installation OMRON GX-ID1621. No tools are required for,
connection to a variety of devices GX-ID1621
Reduced Wiring.
Signal line wiring has been reduced so that the,
Terminal can be mounted closer to sensors and,
other devices.
Relay Box not Required.
Environment-resistant, dust-tight, drip-proof,
construction (IP67) enables direct on-site,
mounting.
Easier Maintenance.
Significant reductions not only in setup time but also,
maintenance time OMRON GX-ID1621.
Reduced Space, Improved Operability,
Compact design (160 x 54 mm (W x H)) (8-point models).
Settings and connections can be performed using,
the switch and connectors on the front side of the Terminal.
System Configuration. Name: MIL Connectors.
Specifications: Outputs; 32 outputs ; PNP; --.
"Easy" and "Flexible" system expansion,
with linked CC-Link and CompoNet OMRON GX-ID1621.
Branching is easily made with CompoNet.
Wiring material cost can be reduced.
Bit-level I/O distribution reduces,
wiring in the system.
A wide variety of CompoNet Slave Units,
contribute to system size reduction.
Seven-segment Display on the Gateway Unit,
helps to detect errors on site OMRON EtherCAT Remote I/O Terminals.
The Participation Flags and Communications,
Error Flags can be checked at the Host,
Controller to detect the location and,
content of the error OMRON EtherCAT Remote I/O Terminals. Input capacity: 16 points.
Internal I/O common: NPN.
ON voltage: 15 VDC min. (between each in,
put terminal and the V terminal).
OFF voltage: 5 VDC max. (between each in,
put terminal and the V terminal).
OFF current: 1 OMRON EtherCAT Remote I/O Terminals. 0 mA max.
Input current: 6.0 mA max./input (at 24-VDC),
3.0 mA min./input (at 17-VDC).
ON delay: 0.1 ms max.
OFF delay: 0.2 ms max.
Input filter value: Without filter, 0.5 ms,
1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms.
(Default setting: 1ms)
Number of circuits per common: 16 points/common.
Input indicators: LED display (yellow).
Isolation method: No isolation.
I/O power supply method: Supplied from unit power supply.
Input device supply current: 50 mA/point.
Unit power supply current consumption: 150 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
e-CON Connector insertion durability: 50 times.
Weight: 140 g max.
Expansion functions: No.
Short-circuit protection function: Available.
(Operates at 50 mA/point min.)
Easy wiring using industry standard,
e-CON connectors.
Special wiring tool is not necessary.
Digital I/O terminal with industry,
standard e-CON connectors.
A common termiinal is provided for,
each connector GX-ID1621.
The I/O terminal and the sensors can,
be connected directly.
Input response time can be switched for,
high-speed processing.
Selectable node address setting methods:
setting with rotary,
sswitch and with tool software OMRON GX-ID1621.
When setting the nodes with rotary switch,
setting is easy and node identification,
becomes possible for maintenance.