Cable with connector (1 to 2) /G79-O_C-_, G79-I_C-_.
L size: A, 1000mm; B, 750mm.
Input use.
Cable and loose wire cable with loose wire pressing connecting terminal,
Connector cable, MITSUBISHI motor produced PLC connection cable. Input capacity: 16 points.
Internal I/O common: NPN.
ON voltage: 15 VDC min GT1-ID16-HD PROGRAMMING MANUAL.
(between each input terminal and the V terminal)
OFF voltage: 5 VDC max
GT1-ID16-HD
(between each input terminal and the V terminal)
OFF current: 1.0 mA max.
Input current: 6.0 mA max./input (at 24-VDC);
3.0 mA min./input (at 17-VDC).
ON delay: 0.1 ms max.
OFF delay: 0.2 ms max.
Input filter value: Without filter, 0.5 ms, 1 ms,
2 ms, 4 ms, 8 ms, 16 ms, 32 ms (Default setting: 1 ms).
Number of circuits per common: 16 inputs/common GT1-ID16-HD PROGRAMMING MANUAL.
Input indicators: LED display (yellow).
Isolation method: Photocoupler isolation.
I/O power supply method: Supply by I/O power supply.
Unit power supply current consumption: 90 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
I/O power supply current con sumption: 5 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
Weight: 180 g max.
Expansion functions: Enabled GT1-ID16-HD PROGRAMMING MANUAL.
Short-circuit protection function: No.
High-speed digital I/O terminal with the,
screw type terminal block for EtherCAT,
communications.
Detachable screw terminal block facilitates,
the maintenance.
The expansion unit can be connected.
(One expansion unit per one I/O terminal unit.)
Input/output point can be flexibly increased,
depending on the system.
Input response time can be switched for,
high-speed processing.
Selectable node address setting methods:
setting with rotary switch and with tool software.
When setting the nodes with rotary switch,
setting is easy and node identification becomes,
possible for maintenance. I/O classification: Analog output.
I/O points: 4.
I/O connections: Molex connector.
Power supply voltage: 24 VDC.
I/O specification: 0 to 5 V, 11 to 5 V, 0 to 10 V, -10 to 10 V GT1-ID16-HD Manual.
Analog Input/Output Units Compatible with MULTIPLE I/O TERMINAL.
Input block incorporates connectors that can be easily,
mounted or dismounted. (GT1-AD08MX, GT1-DA04MX)
8 or 4 inputs.
4 outputts GT1-ID16-HD Manual.
High resolution of 1/6,000.
High conversion speed of 8 ms/8 points or 4 ms/4 points.
DIN track mounting.